Kees K SERIES AIR DIFFUSERS WITH ADJUSTABLE AIR PATTERN Manuel d'utilisateur Page 2

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 2
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 1
Project
Engineer
Architect
Contractor
Dwg. No.
Date
Location
09/98
KEES INCORPORATED
400 S. Industrial Dr.
z P.O. Box L
Elkhart Lake, WI 53020
Phone: (920) 876-3391
Fax: (920) 876-3065
Website: www.kees.com
POSSIBLE CAUSES OF "DUMPING"
WITH THE ADDITION OF
THE CENTER TEE
EXTENSION
BLADES POSITIONED
SO BOTH AIRSTREAMS COLLIDE.
(SOLUTION - REPOSITION BLADES
TO APPROPRIATE POSITION. SEE
FRONT PAGE).
OBSTRUCTION BELOW THE BOTTOM OF
THE DIFFUSER. (SOLUTION - MOUNT
DIFFUSER FLUSH WITH CEILING).
CENTER TEE BY OTHERS
BUT NONE INSTALLED.
(SOLUTION - INSTALL CENTER TEE).
BLADES SET FOR 1 WAY THROW.
CENTER TEE BY OTHERS TOO SHORT.
(SOLUTION - INSTALL CENTER
TEE EXTENSION).